22
Features:
• Designed to the latest European EN 50171 Specification for Emergency Lighting
• True double conversion and PWM technology
• Inverter stage output galvanic isolation transformer included
• Up to 91% efficiency
• Capable of 120% continuous overload to meet European Emergency
Lighting regulations
• Parallel mode operation (optional) (hot standby, redundant, symmetric parallel)
• Large charger for faster recharge of batteries
• Maintenance bypass (for complete isolation of the inverter during maintenance)
• Unique Inverter design to suit high inrush lighting loads
• Bypass to load (changeover mode) user selection
• LCD panel providing accurate detailed information about load, Batteries and
Inverter with advanced diagnostics
• RS232 and dry contacts for communication and remote monitoring
PowerPro EL 200 Series
Three Phase Input & Single Phase Output Static Inverter
High Performance Static Inverter
Model EL210 EL215 EL220
Power Rating kVA/kW 10 / 8 15 / 12 20 / 16
Power Factor 0.8
Input
Voltage / Tolerance 230/400 VAC 3phase, 4wires, +ground, +/- 15%
By-pass Voltage 230 VAC single phase
Input Frequency 50Hz +/- 5%
Max RFI EN50091-2 Class A
Output
Voltage 230 VAC single phase
Voltage Stability Static (balanced load) +/-1%, Static (unbalanced load) +/-2%, Dynamic (stop load 0-100%) +/-5%
Voltage Recovery Time After step load 0-100% max. 20ms
Frequency 50Hz
Frequency Tolerance Line synchronised +/- 1% / free running +/- 0.2%
Efficiency at 100% Load >87-91%
Crest Factor 3:1
Short Circuit Protection Electronic short circuit
Overload Capacity 120% continuous, 150% load 10min. 180% 1min, 200% for 1 sec
Total Harmonic Distortion (THD) Linear Load <3% / non linear load (75%NP and CF 3:1) <5%
Batteries
Type Sealed Lead Acid – Maintenance Free
Number of 12V Blocks 30
Float Charging Voltage 405
End of Discharge Voltage 300VDC
Battery Ambient Temperature 25°C
Battery Protection Circuit breaker
Battery Test Automatic battery test once a week
General
Serial Communication Dry contacts plus RS232
Software T-Mon standard / SNMP module optional
Protection Degree IP41
Ambient Operating Temperature / Altitude 0°C to 40°C / <1000m (above sea level)
Standard Emergency Lighting EN 50171
Ventilation Forced air cooling
Relative Humidity 90% max (non-condensing)
Acoustic Noise at 1m distance <56 dbA
Weight (kgs) 200 210 240
Dimensions (mm) w x d x h 520x715x1170