BPC PowerMaster Specifiche Pagina 17

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 40
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 16
Features:
True double conversion technology
Galvanic isolation transformer at the inverter stage
High reliability with low maintenance
Pure sine wave output
High efficiency up to 90%
Intelligent battery monitoring to maximise service life
Automatic static bypass switch providing no-break transfer
Capability for parallel redundant operation if required
LCD panel providing real time operational status
Recorded power history logs
RS232 and dry contacts for communication and remote monitoring
Input / output customisation is available
Technical Specification
17
PowerPro HP 200 Series
Three Phase Input & Single Phase Output
Online Double Conversion UPS
High Performance Advanced Power Protection
Model HP206 HP207 HP210 HP215XA HP220XA HP230XA
Power Rating kVA/kW 6 / 4.2 7 / 4.9 10 / 7 15 / 10.5 20 / 14 30 / 21
Input
Voltage / Tolerance 230/400VAC Three Phase +N / +/- 15%
Bypass Voltage / Tolerance 230Vac +/- 10%
Maximum Current absorbed from mains 3x 12A 3x 17A 3x 17A 3x 25A 3x 25A 3x 50A
Input Frequency / Tolerance 50Hz +/- 5%
EMI EN50091-2 Class A
Output
Waveform / Output THD True sine wave / <3% THD
Nominal Voltage 230Vac
Voltage Stability +/- 1%
Voltage Dynamic Step Load (0 to 100% to 0) +/- 5%
Frequency / Frequency Stability 50Hz Line synchronised +/- 1% / Free running +/- 0.2%
On Line Mode Efficiency at full load >90%
Economy Mode Efficiency at full load >98%
Crest Factor 3:1
Over Load Protection 100% - 125% load for 10min. / 125% - 150% load for 1min. / >150% load bypass
Short Circuit Protection Electronic short circuit protection
Batteries
Type Sealed Lead Acid – Maintenance Free
Number of 12V Blocks 20 20 20 30 30 30
Float Charging Voltage 270Vdc 270Vdc 270Vdc 405Vdc 405Vdc 405Vdc
End of Discharge Voltage 200Vdc 200Vdc 200Vdc 300Vdc 300Vdc 300Vdc
Equalising Boost Charge Voltage 280Vdc 280Vdc 280Vdc 422Vdc 422Vdc 422Vdc
Battery Location Internal
Battery Test Optional Automatic
General
Protection Degree IP21
Communication Dry contacts plus RS232 / Options for SNMP & Modbus
Software T-Mon supplied as standard
Temperature/Relative Humidity/Altitude 0°C to 40° C / 90% max (non-condensing) / <1000m (above sea level)
Acoustic Noise at 1m Distance <42dbA <55dbA
Heat Dissipation at Nominal Load (kW) 0.62 0.78 1.04 1.57 2.09 3.14
Dimensions (mm) w x d x h 265 x 740 x 950 505 x 650 x 1225
Weight without Batteries (kgs) 106 110 125 190 200 230
The British Power Conversion Company
Picture shows HP206 and HP210 models
Vedere la pagina 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 39 40

Commenti su questo manuale