BPC PowerMaster Specifiche Pagina 21

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 40
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 20
Features:
Designed to the latest European EN 50171 Specification for Emergency
Lighting
True double conversion and PWM technology
Inverter stage output galvanic isolation transformer included
Up to 91% efficiency
Capable of 120% continuous overload to meet European Emergency
Lighting regulations
Parallel mode operation (optional) (hot standby, redundant, symmetric
parallel)
Large charger for faster recharge of batteries
Maintenance bypass (for complete isolation of the inverter during
maintenance)
Unique inverter design to suit high inrush lighting loads
Bypass to load (changeover mode) user selectable
LCD panel providing accurate detailed information about load,
batteries and inverter with advanced diagnostics
RS232 and dry contacts for communication and remote monitoring
PowerPro EL 100 Series
Single Phase Input & Output Online Static Inverter
High Performance Static Inverter
21
Model EL104 EL105 EL106 EL108 EL110 EL112
Power Rating kVA/kW 4 / 3.2 5 / 4 6 / 4.8 8 / 6.4 10/8 12.5 / 10
Power Factor 0.8
Input
Voltage / Tolerance 230 VAC single phase, +/- 15%
By-pass Voltage 230 VAC single phase
Input Frequency 50Hz +/- 5%
Max RFI EN50091-2 Class A
Output
Voltage 230 VAC single phase
Voltage Stability Static (balanced load) +/-1%, Static (unbalanced load) +/-2%, Dynamic (step load 0-100%) +/-5%
Voltage Recovery Time After step load 0-100% max. 20ms
Frequency 50Hz
Frequency Tolerance Line synchronised +/- 1% / free running +/- 0.2%
Efficiency at 100% Load >87-91%
Crest Factor 3:1
Short Circuit Protection Electronic short circuit
Overload Capacity 120% continuous, 150% load 10min. 180% 1min, 200% for 1 sec
Total Harmonic Distortion (THD) Linear Load <3% / non linear load (75%NP and CF 3:1) <5%
Batteries
Type Sealed Lead Acid – Maintenance Free
Number of 12V Blocks 16 18 20
Float Charging Voltage 216Vdc 243Vdc 270Vdc
End of Discharge Voltage 160Vdc 180Vdc 200Vdc
Battery Ambient Temperature 25°C
Battery Protection Circuit breaker
Battery Test Automatic battery test once a week
General
Serial Communication Dry contacts plus RS232
Software T-Mon standard / SNMP module optional
Protection Degree IP41
Ambient Operating Temperature / Altitude 0°C to 40°C / <1000m (above sea level)
Standard Emergency Lighting EN 50171
Ventilation Forced air cooling
Acoustic Noise at 1m distance <56 dbA
Weight (kgs) 85 95 110 125 150 155
Dimensions (mm) w x d x h 300x500x1220
Technical Specification
The British Power Conversion Company
Vedere la pagina 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 39 40

Commenti su questo manuale

Nessun commento